APPLICABILITY OF VENTILATION SYSTEMS FOR REDUCING THE INDOOR RADON CONCENTRATION
M. Jiránek, V. Kačmaříková
Jazyk angličtina Země Velká Británie
Typ dokumentu časopisecké články
PubMed
33089328
DOI
10.1093/rpd/ncaa148
Knihovny.cz E-zdroje
- MeSH
- bydlení MeSH
- radioaktivní látky znečišťující vzduch * analýza MeSH
- radon * analýza MeSH
- větrání MeSH
- znečištění vzduchu ve vnitřním prostředí * analýza MeSH
- Publikační typ
- časopisecké články MeSH
An analysis is presented of the ability of balanced mechanical ventilation systems to reduce the radon concentration in residential buildings efficiently. The analysis takes into account the following parameters: radon supply rate into the building, ventilation intensity, required indoor radon concentration and energy consumption. It is shown that the applicability of ventilation systems is limited mainly by energy consumption. Ventilation systems can be considered energetically acceptable if the ventilation intensity does not exceed 0.6 h-1, i.e. radon supply rate should not exceed 60 Bq/m3h for a required indoor radon concentration of 100 Bq/m3. Energy consumption can be significantly reduced by operating the ventilation system in a cyclic mode. Simulating the behavior of ventilation systems in time has been found as a useful tool for their design. In order to express by one parameter energy consumption and radon reduction, a completely new quantity-the 'radon-related energy need' has been proposed.
Citace poskytuje Crossref.org
- 000
- 00000naa a2200000 a 4500
- 001
- bmc21019789
- 003
- CZ-PrNML
- 005
- 20210830101402.0
- 007
- ta
- 008
- 210728s2020 xxk f 000 0|eng||
- 009
- AR
- 024 7_
- $a 10.1093/rpd/ncaa148 $2 doi
- 035 __
- $a (PubMed)33089328
- 040 __
- $a ABA008 $b cze $d ABA008 $e AACR2
- 041 0_
- $a eng
- 044 __
- $a xxk
- 100 1_
- $a Jiránek, Martin $u Czech Technical University, Faculty of Civil Engineering, Thákurova 7, 166 29 Praha 6, Czech Republic
- 245 10
- $a APPLICABILITY OF VENTILATION SYSTEMS FOR REDUCING THE INDOOR RADON CONCENTRATION / $c M. Jiránek, V. Kačmaříková
- 520 9_
- $a An analysis is presented of the ability of balanced mechanical ventilation systems to reduce the radon concentration in residential buildings efficiently. The analysis takes into account the following parameters: radon supply rate into the building, ventilation intensity, required indoor radon concentration and energy consumption. It is shown that the applicability of ventilation systems is limited mainly by energy consumption. Ventilation systems can be considered energetically acceptable if the ventilation intensity does not exceed 0.6 h-1, i.e. radon supply rate should not exceed 60 Bq/m3h for a required indoor radon concentration of 100 Bq/m3. Energy consumption can be significantly reduced by operating the ventilation system in a cyclic mode. Simulating the behavior of ventilation systems in time has been found as a useful tool for their design. In order to express by one parameter energy consumption and radon reduction, a completely new quantity-the 'radon-related energy need' has been proposed.
- 650 12
- $a radioaktivní látky znečišťující vzduch $x analýza $7 D000396
- 650 12
- $a znečištění vzduchu ve vnitřním prostředí $x analýza $7 D016902
- 650 _2
- $a bydlení $7 D006798
- 650 12
- $a radon $x analýza $7 D011886
- 650 _2
- $a větrání $7 D014691
- 655 _2
- $a časopisecké články $7 D016428
- 700 1_
- $a Kačmaříková, Veronika $u Czech Technical University, Faculty of Civil Engineering, Thákurova 7, 166 29 Praha 6, Czech Republic
- 773 0_
- $w MED00004029 $t Radiation protection dosimetry $x 1742-3406 $g Roč. 191, č. 2 (2020), s. 202-208
- 856 41
- $u https://pubmed.ncbi.nlm.nih.gov/33089328 $y Pubmed
- 910 __
- $a ABA008 $b sig $c sign $y p $z 0
- 990 __
- $a 20210728 $b ABA008
- 991 __
- $a 20210830101402 $b ABA008
- 999 __
- $a ok $b bmc $g 1690573 $s 1140235
- BAS __
- $a 3
- BAS __
- $a PreBMC
- BMC __
- $a 2020 $b 191 $c 2 $d 202-208 $e 2020Nov27 $i 1742-3406 $m Radiation protection dosimetry $n Radiat Prot Dosimetry $x MED00004029
- LZP __
- $a Pubmed-20210728