A comparison between tracer gas and aerosol particles distribution indoors: The impact of ventilation rate, interaction of airflows, and presence of objects
M. Bivolarova, J. Ondráček, A. Melikov, V. Ždímal,
Jazyk angličtina Země Anglie, Velká Británie
Typ dokumentu srovnávací studie, časopisecké články
PubMed
28378912
DOI
10.1111/ina.12388
Knihovny.cz E-zdroje
- MeSH
- aerosoly analýza MeSH
- modely anatomické rozkládací MeSH
- plyny analýza MeSH
- pohyb vzduchu MeSH
- větrání * MeSH
- znečištění vzduchu ve vnitřním prostředí * MeSH
- Publikační typ
- časopisecké články MeSH
- srovnávací studie MeSH
The study investigated the separate and combined effects of ventilation rate, free convection flow produced by a thermal manikin, and the presence of objects on the distribution of tracer gas and particles in indoor air. The concentration of aerosol particles and tracer gas was measured in a test room with mixing ventilation. Three layouts were arranged: an empty room, an office room with an occupant sitting in front of a table, and a single-bed hospital room. The room occupant was simulated by a thermal manikin. Monodisperse particles of three sizes (0.07, 0.7, and 3.5 μm) and nitrous oxide tracer gas were generated simultaneously at the same location in the room. The particles and gas concentrations were measured in the bulk room air, in the breathing zone of the manikin, and in the exhaust air. Within the breathing zone of the sitting occupant, the tracer gas emerged as reliable predictor for the exposure to all different-sized test particles. A change in the ventilation rate did not affect the difference in concentration distribution between tracer gas and larger particle sizes. Increasing the room surface area did not influence the similarity in the dispersion of the aerosol particles and the tracer gas.
Citace poskytuje Crossref.org
- 000
- 00000naa a2200000 a 4500
- 001
- bmc19001280
- 003
- CZ-PrNML
- 005
- 20190121101958.0
- 007
- ta
- 008
- 190107s2017 enk f 000 0|eng||
- 009
- AR
- 024 7_
- $a 10.1111/ina.12388 $2 doi
- 035 __
- $a (PubMed)28378912
- 040 __
- $a ABA008 $b cze $d ABA008 $e AACR2
- 041 0_
- $a eng
- 044 __
- $a enk
- 100 1_
- $a Bivolarova, M $u Department of Civil Engineering, International Centre for Indoor Environment and Energy, Technical University of Denmark, Lyngby, Denmark.
- 245 12
- $a A comparison between tracer gas and aerosol particles distribution indoors: The impact of ventilation rate, interaction of airflows, and presence of objects / $c M. Bivolarova, J. Ondráček, A. Melikov, V. Ždímal,
- 520 9_
- $a The study investigated the separate and combined effects of ventilation rate, free convection flow produced by a thermal manikin, and the presence of objects on the distribution of tracer gas and particles in indoor air. The concentration of aerosol particles and tracer gas was measured in a test room with mixing ventilation. Three layouts were arranged: an empty room, an office room with an occupant sitting in front of a table, and a single-bed hospital room. The room occupant was simulated by a thermal manikin. Monodisperse particles of three sizes (0.07, 0.7, and 3.5 μm) and nitrous oxide tracer gas were generated simultaneously at the same location in the room. The particles and gas concentrations were measured in the bulk room air, in the breathing zone of the manikin, and in the exhaust air. Within the breathing zone of the sitting occupant, the tracer gas emerged as reliable predictor for the exposure to all different-sized test particles. A change in the ventilation rate did not affect the difference in concentration distribution between tracer gas and larger particle sizes. Increasing the room surface area did not influence the similarity in the dispersion of the aerosol particles and the tracer gas.
- 650 _2
- $a aerosoly $x analýza $7 D000336
- 650 _2
- $a pohyb vzduchu $7 D000392
- 650 12
- $a znečištění vzduchu ve vnitřním prostředí $7 D016902
- 650 _2
- $a plyny $x analýza $7 D005740
- 650 _2
- $a modely anatomické rozkládací $7 D008348
- 650 12
- $a větrání $7 D014691
- 655 _2
- $a srovnávací studie $7 D003160
- 655 _2
- $a časopisecké články $7 D016428
- 700 1_
- $a Ondráček, J $u Laboratory of Aerosol Chemistry and Physics, Institute of Chemical Process Fundamentals of the CAS, Prague, Czech Republic.
- 700 1_
- $a Melikov, A $u Department of Civil Engineering, International Centre for Indoor Environment and Energy, Technical University of Denmark, Lyngby, Denmark.
- 700 1_
- $a Ždímal, V $u Laboratory of Aerosol Chemistry and Physics, Institute of Chemical Process Fundamentals of the CAS, Prague, Czech Republic.
- 773 0_
- $w MED00002225 $t Indoor air $x 1600-0668 $g Roč. 27, č. 6 (2017), s. 1201-1212
- 856 41
- $u https://pubmed.ncbi.nlm.nih.gov/28378912 $y Pubmed
- 910 __
- $a ABA008 $b sig $c sign $y a $z 0
- 990 __
- $a 20190107 $b ABA008
- 991 __
- $a 20190121102216 $b ABA008
- 999 __
- $a ok $b bmc $g 1365167 $s 1039403
- BAS __
- $a 3
- BAS __
- $a PreBMC
- BMC __
- $a 2017 $b 27 $c 6 $d 1201-1212 $e 20170504 $i 1600-0668 $m Indoor air $n Indoor air $x MED00002225
- LZP __
- $a Pubmed-20190107