Dealing with the increased radon concentration in thermally retrofitted buildings

. 2014 Jul ; 160 (1-3) : 43-7. [epub] 20140411

Jazyk angličtina Země Velká Británie, Anglie Médium print-electronic

Typ dokumentu časopisecké články, práce podpořená grantem

Perzistentní odkaz   https://www.medvik.cz/link/pmid24729563

The influence of energy-saving measures on indoor radon concentration has been studied on the basis of a family house made of clinker concrete wall panels containing from 1000 up to 4000 Bq kg(-1) of 226Ra. Thermal retrofitting based on installing external thermal insulation composite system on the building envelope and replacing existing windows by new ones decreased the annual energy need for heating 2.8 times, but also reduced the ventilation rate to values<0.1 h(-1). As a consequence, the 1-y average indoor radon concentration values increased 3.4 times from 337 to 1117 Bq m(-3). The additional risk of lung cancer in the thermally retrofitted house increased to a value that is 125 % higher than before conversion. Methods for dealing with this enhanced risk by increasing the ventilation rate are discussed. Recovery of investments and the energy consequences of increased ventilation are studied in a long-term perspective.